1. Fire Exit Sign Design & Specifications (IS 9457:2005)
Yes
No
Are all fire exit signs minimum 300mm × 150mm in size as per IS 9457:2005?
[IS 9457:2005 - Clause 4.1]
Yes
No
Do exit signs use correct colors: Green background (Pantone 347C) with white text and symbols?
[IS 9457:2005 - Clause 5.2]
Yes
No
Are letter heights minimum 25mm for "EXIT" text with appropriate stroke width (1:8 ratio)?
[IS 9457:2005 - Clause 6.1]
Yes
No
Are pictogram symbols minimum 100mm × 100mm and compliant with ISO 3864-1 standards?
[IS 9457:2005 - Clause 4.3]
Yes
No
Are sign materials fire-resistant (Class A2 rating) and UV-stable for 10+ years?
[IS 9457:2005 - Clause 3.2]
2. Sign Placement & Installation (NBCC 2016)
Yes
No
Are exit signs installed above every designated emergency exit door?
[NBCC 2016 - Part 4, Section 2.4.1]
Yes
No
Are signs mounted at height 2.1m to 2.4m above finished floor level?
[NBCC 2016 - Part 4, Section 2.4.2]
Yes
No
Are directional signs placed at maximum 30-meter intervals in corridors?
[NBCC 2016 - Part 4, Section 2.4.3]
Yes
No
Are signs visible from minimum 20 meters with unobstructed 120° viewing angle?
[NBCC 2016 - Part 4, Section 2.4.4]
Yes
No
Are signs installed perpendicular to primary viewing direction with secure mounting?
[NBCC 2016 - Part 4, Section 2.4.5]
3. Emergency Lighting & Illumination (Indian Fire Service)
Yes
No
Do illuminated exit signs provide minimum 50 lux on sign face during normal and emergency conditions?
[Fire Service Guidelines 2018]
Yes
No
Is emergency backup power provided for minimum 3 hours continuous operation?
[NBCC 2016 - Part 8, Section 5.3]
Yes
No
Are photoluminescent signs compliant with DIN 67510 with sufficient charging periods?
[BIS Guidelines 2019]
Yes
No
Is emergency lighting tested monthly with documentation maintained?
[Fire Service Regulations]
4. Exit Route Compliance & Accessibility
Yes
No
Are all exit routes kept permanently free from obstructions and locked doors?
[NBCC 2016 - Part 4, Section 2.2.1]
Yes
No
Do exit doors open in direction of egress without keys or special knowledge?
[NBCC 2016 - Part 4, Section 2.3.1]
Yes
No
Are exit widths adequate for occupancy load (minimum 900mm for single leaf doors)?
[NBCC 2016 - Part 4, Section 2.2.3]
Yes
No
Are non-exit doors marked "NOT AN EXIT" or similar appropriate marking?
[IS 9457:2005 - Clause 7.2]
5. Building-Specific Requirements
Yes
No
High-rise buildings (>15m): Are illuminated signs mandatory with dual power supply systems?
[NBCC 2016 - Part 4, Section 3.1]
Yes
No
Assembly buildings (>300 occupants): Are exit capacity signs showing person capacity installed?
[NBCC 2016 - Part 4, Section 3.2]
Yes
No
Healthcare facilities: Are special evacuation procedures and disabled evacuation signs provided?
[NBCC 2016 - Part 9, Section 2.4]
Yes
No
Industrial facilities: Are hazard-specific evacuation routes and assembly points clearly marked?
[Factory Act Guidelines]
6. Assembly Point & Emergency Equipment Signage
Yes
No
Are emergency assembly points clearly marked with green background signs visible from 50 meters?
[Fire Service Guidelines]
Yes
No
Are fire extinguisher locations marked with red background signs (RAL 3001) per IS 12349?
[IS 12349:1988 - Color Standards]
Yes
No
Are first aid stations marked with white cross on green background as per ISO 3864 standards?
[BIS Adoption of ISO Standards]
Yes
No
Are evacuation maps posted at building entrances with "You Are Here" marking?
[NBCC 2016 - Part 4, Section 2.5]
7. Maintenance & Testing Requirements
Yes
No
Is monthly visual inspection conducted for sign damage, obstruction, or visibility issues?
[Fire Service Maintenance Protocol]
Yes
No
Is quarterly cleaning of sign faces and emergency lighting fixtures performed?
[NBCC Maintenance Guidelines]
Yes
No
Is annual electrical testing of emergency backup systems documented with certificates?
[Electrical Safety Guidelines]
Yes
No
Are maintenance logs maintained for regulatory inspections and insurance requirements?
[Insurance Council Guidelines]
8. Documentation & Compliance Certificates
Yes
No
Are material certificates available from BIS-approved manufacturers?
[BIS Certification Requirements]
Yes
No
Is Fire No Objection Certificate (NOC) obtained from local fire department?
[Fire Service Approval]
Yes
No
Are installation completion certificates from certified safety consultants available?
[Professional Certification]
Yes
No
Are as-built drawings and specifications updated and maintained for future reference?
[Building Authority Requirements]